1. Electrically Defeating the Combustion Safeguard (Jumping It Out)Whether the combustion safeguard relay is bypassed for maintenance purposes or, even worse, to eliminate the nuisance of a system shutdown, this remains one of the biggest problems with combustion system safety. Defeating the safeguard means there will be a continuous signal to the control system that everything is okay, which allows your gas safety-shutoff valves to remain open even if there are serious problems in maintaining good combustion. If the jumpers are in place to prevent nuisance shutdowns, you must solve the underlying combustion problem. Do not bypass the very safety device that is telling you that you have a problem. Employee training and strictly enforced procedures are two solutions. 2. Using Multiple Sensors to Allow One Combustion Safeguard to Monitor Multiple Flame SignalsUsing multiple sensors and associated relay circuitry to allow one combustion safeguard to monitor multiple flame signals is a more subtle version of jumping it out. This problem usually is seen on piloted burners where one sensor cannot see both the main and pilot flames from a single mounting location. You may think everything is working fine until you realize that the associated relay circuitry is defeating the safe-start check for the main flame sensor by switching that sensor off during the ignition sequence of the burner. This prevents the combustion safeguard from detecting a failed sensor. Don’t forget that some sensors can fail in the “on” position. Replace these dangerous circuits with a combustion safeguard specifically designed to monitor two flame sensors, or use two separate combustion safeguard devices. 3. Mechanically Defeating the Combustion SafeguardThis one is always difficult to believe. However, you still can find operations that use a mechanical device to provide a permanent reset to the combustion safeguard. I have seen this done with a nail used to wedge a reset switch permanently “on,” and I have even seen a welding rod bent and positioned so that it permanently holds in the reset switch. More sophisticated combustion safeguards prevent this dangerous game by monitoring reset switches to ensure they are not permanently engaged (and signaling an alarm condition if they are). 4. Improperly Mounting The Flame SensorImproperly mounting the flame sensor is yet another way some operators circumvent safety controls. A flame sensor must be mounted to sense only the flame it is intended to monitor. Failure of the sensor to detect the flame is frustrating (because you get continual nuisance shutdowns of the combustion system), but at least it is a safe condition since it causes the safety-shutoff valves to close. A sensor that detects the wrong flame (such as the flame of another burner in the oven) or otherwise falsely indicates flame when a flame does not exist is truly dangerous. For either condition, the sensors must be repositioned to detect only the flames they are intended to monitor. This is true for both line-of-sight sensors, which detect ultraviolet and infrared emissions, and flame-rod sensors, which detect flame using the electrical conduction properties of a flame envelope. If this cannot be done, there is a chance your system is using the wrong sensor. 5. Selecting the Wrong Sensor Has ConsequencesThe sensor should be related to the burner design, oven or furnace design and the user’s overall process (roughly in that order). Burners that do not retain flame near the base of the burner (i.e., the flame “walks” off the base of the burner) will not work well with flame rods. Processes that produce excessive moisture may not work well with ultraviolet because water vapor absorbs ultraviolet emissions. Infrared sensors are subject to “wash-out” in the presence of high background flame and may sense glowing oven surfaces as flame. While a combustion specialist can certainly help in determining the best sensor for your application, testing the combustion safeguard is the best way to ensure that you have selected the most appropriate sensor. Peace of mind knowing that your personnel, your operation and your business are safer is well worth the small investment needed to meet code and is far less expensive than dealing with the consequences of an oven filled with gas and air that finds a source of ignition. Steve Ogonek is currently a managing partner at Thermal Products & Solutions. Contact TPS. Given the complexity and diversity of combustion applications, this article is not intended to relieve any user and/or company from taking it upon themselves to gain a thorough understanding of NFPA codes and standards, and the requirements for compliance of the user and/or company’s own operation. As such, the author and any company named herein disclaim liability for any personal injury or property or other damages of any nature whatsoever, whether special, indirect, consequential or compensatory, directly or indirectly resulting from the publication, use of or reliance on this article.
|
|
||||||||||||||||||||||||